A supplier may describe a filter as “H14 HEPA,” while another labels the same performance level “ISO 45 H.” If you are specifying filters for a cleanroom, pharmaceutical facility, laboratory, or industrial HVAC system, that difference can affect acceptance criteria, test documentation, and ultimately your project schedule.
This guide explains how EN 1822 and ISO 29463 classify EPA, HEPA, and ULPA filters, how their filter classes compare, and what you should require in a purchase specification and test report. The key point is simple: the two standards are closely related, but an efficiency threshold alone does not make two filters fully equivalent.
What Are EN 1822 and ISO 29463?
EN 1822 is the European standard for testing and classifying high-efficiency air filters. It divides filters into EPA, HEPA, and ULPA groups and uses familiar class designations such as E11, H13, H14, and U15.
ISO 29463 is the international standard series for EPA, HEPA, and ULPA filters. It covers filter requirements, test methods, classification, and marking, and it provides a global framework for comparing high-efficiency filter performance.
Both standards classify filters according to performance at the most penetrating particle size (MPPS). However, they are not automatically interchangeable: their class structures, test-method details, and documentation expectations can differ.
| Aspect | EN 1822 | ISO 29463 |
|---|---|---|
| Standard type | European standard | International standard series |
| Common class format | E10, H13, H14, U15 | ISO 15 E, ISO 35 H, ISO 45 H, ISO 55 U |
| Classification basis | MPPS efficiency and penetration | MPPS efficiency and penetration |
| Typical use | European project specifications and familiar H13/H14 language | International procurement and cross-border supplier qualification |
| Practical caution | Check the exact version and test requirements | Check the exact part, version, and permitted test methods |
EPA, HEPA, and ULPA: What Do They Mean?
Before comparing the standards, it helps to understand the three filter groups.
- EPA filters are efficient particulate air filters, commonly used where high filtration is required but HEPA-level performance is not necessary.
- HEPA filters are high-efficiency particulate air filters, widely used in cleanrooms, hospitals, pharmaceutical production, laboratories, and critical HVAC applications.
- ULPA filters are ultra-low penetration air filters, typically selected for semiconductor, microelectronics, and other applications requiring extremely low particle penetration.
In EN 1822, H13 filters must achieve at least 99.95% integral efficiency at MPPS, while H14 filters must achieve at least 99.995%. ULPA filters begin at U15, where the required efficiency is higher still.
Do not treat “HEPA” as a generic marketing term. A true HEPA or ULPA classification should be supported by a defined standard, test airflow, MPPS result, and traceable test documentation.
MPPS Explained: The Basis for Classification
MPPS stands for most penetrating particle size. It is the particle size at which a filter medium or complete filter shows its highest penetration—and therefore its lowest efficiency.
Testing at MPPS is more demanding than testing at a single convenient particle size because it evaluates the filter at its weakest point. This is why both EN 1822 and ISO 29463 use MPPS performance as the basis for classification.
The relationship between efficiency and penetration is:
Penetration=100%−Efficiency
For example, a filter with 99.995% efficiency has a penetration of 0.005%. That small difference matters greatly in a cleanroom, where even low particle penetration can affect product yield, contamination control, and validation outcomes.
EN 1822 Filter Classes Explained
EN 1822 uses three groups:
- E group: EPA filters
- H group: HEPA filters
- U group: ULPA filters
The most commonly specified HEPA classes are H13 and H14. H13 is often used in general cleanroom and HVAC applications, while H14 is selected where lower particle penetration and tighter leakage control are required.
| EN 1822 class | Filter group | Minimum integral efficiency at MPPS |
|---|---|---|
| E10 | EPA | ≥ 85% |
| E11 | EPA | ≥ 95% |
| E12 | EPA | ≥ 99.5% |
| H13 | HEPA | ≥ 99.95% |
| H14 | HEPA | ≥ 99.995% |
| U15 | ULPA | ≥ 99.9995% |
| U16 | ULPA | ≥ 99.99995% |
| U17 | ULPA | ≥ 99.999995% |
For H and U classes, performance is not only about the average efficiency of the complete filter. Local efficiency and local penetration requirements also apply because a small defect, damaged media area, or poor seal can create a localized leak even when the overall filter efficiency appears acceptable.airfiltration.mann-hummel+1
ISO 29463 Filter Classes Explained
ISO 29463 uses a different naming format. Instead of “H13” or “H14,” you will see designations such as ISO 35 H and ISO 45 H.
The ISO system is based on the same MPPS performance principle as EN 1822, but it includes more granular intermediate classes. This means that not every ISO class has a direct EN 1822 counterpart.
| ISO 29463 class | Filter group | Minimum integral efficiency at MPPS |
|---|---|---|
| ISO 05 E | EPA | ≥ 85% |
| ISO 15 E | EPA | ≥ 95% |
| ISO 25 E | EPA | ≥ 99.5% |
| ISO 35 H | HEPA | ≥ 99.95% |
| ISO 45 H | HEPA | ≥ 99.995% |
| ISO 55 U | ULPA | ≥ 99.9995% |
| ISO 65 U | ULPA | ≥ 99.99995% |
| ISO 75 U | ULPA | ≥ 99.999995% |
ISO 29463 also includes intermediate classes such as ISO 20 E, ISO 30 E, ISO 40 H, and ISO 50 U. These classes do not have direct one-to-one equivalents in EN 1822, which is why a simple conversion table should never be used as the only basis for approval.
EN 1822 vs ISO 29463: Class Conversion Table
The table below shows the closest efficiency-threshold relationship between the two standards. It is useful for early-stage comparison, but it should not replace a technical review of the test method and acceptance criteria.
| EN 1822 class | Closest ISO 29463 threshold | Minimum integral efficiency at MPPS |
|---|---|---|
| E10 | ISO 05 E | ≥ 85% |
| E11 | ISO 15 E | ≥ 95% |
| E12 | ISO 25 E | ≥ 99.5% |
| H13 | ISO 35 H | ≥ 99.95% |
| H14 | ISO 45 H | ≥ 99.995% |
| U15 | ISO 55 U | ≥ 99.9995% |
| U16 | ISO 65 U | ≥ 99.99995% |
| U17 | ISO 75 U | ≥ 99.999995% |
In practice, you may see statements such as “H14 is equivalent to ISO 45 H.” That is acceptable as a simplified efficiency comparison, but it becomes risky if it is used to avoid specifying the standard version, test airflow, aerosol, leakage-test method, or individual filter traceability.
Key Differences: Classification, Testing and Documentation
Although both standards assess performance at MPPS, they differ in how they frame testing and documentation.
1. Classification structure
EN 1822 uses E, H, and U classes such as H13 and H14. ISO 29463 uses ISO class designations such as ISO 35 H and ISO 45 H, with additional intermediate classes that do not map directly to EN 1822.
2. Leakage and local performance
For HEPA and ULPA filters, local performance is critical. A filter can meet the nominal integral efficiency requirement yet fail to meet local leakage requirements if there is a defect in the media, seal, frame, or installation interface.airfiltration.mann-hummel+1
3. Test-method flexibility
ISO 29463 provides an international framework with defined test procedures and marking requirements. EN 1822 remains widely used in European specifications, particularly where H13 and H14 terminology is already embedded in project documents.
4. Procurement documentation
The same nominal class can be presented with very different levels of evidence. For critical applications, you should require the standard version, test airflow, MPPS result, leakage-test method, serial number, and individual test report—not merely a certificate stating “HEPA H14.”
Integral Efficiency vs Local Efficiency: What Buyers Must Check
Many procurement disputes arise because buyers and suppliers use the word “efficiency” without clarifying which measurement they mean.
Integral efficiency describes the performance of the complete filter across its full face area. It is an average measurement of how well the filter removes particles at MPPS.
Local efficiency describes performance at a specific scanned area of the filter. It is used to identify localized penetration caused by media defects, pinholes, damaged pleats, or sealing problems.
For H and U filters, both values matter. A high integral efficiency result does not eliminate the need to verify local leakage performance, especially for pharmaceutical, semiconductor, and validated cleanroom applications.
Type Testing vs Individual Filter Testing
A type test demonstrates that a filter design or product family can achieve the stated performance under controlled test conditions. It is usually performed on representative samples.
An individual test verifies the performance of the specific filter being supplied. It confirms that the actual unit meets the required efficiency and leakage criteria before shipment.
These tests serve different purposes. A type-test report can support product qualification, but it cannot prove that every individual filter in a shipment is defect-free. For critical projects, specify individual testing and serial-number traceability.
What a Compliant HEPA or ULPA Test Report Should Include?
When reviewing a HEPA or ULPA filter test report, look for more than a class label. A credible report should allow you to connect the physical filter to its measured performance.
A complete test report should include:
- Manufacturer name and test location
- Filter model, dimensions, and serial number or batch number
- Applicable standard and version, such as EN 1822-1:2019 or ISO 29463-1:2024
- Declared filter class
- Rated or test airflow
- Test aerosol and MPPS information
- Integral efficiency or penetration result
- Local efficiency or leakage-test method and result
- Initial pressure drop at the stated airflow
- Test date and conformity conclusion
For validated environments, require that the report is traceable to the individual filter serial number. A generic certificate without measured data is not a substitute for a proper test report.
How to Specify EN 1822 or ISO 29463 in a Purchase Order?
If you are preparing a filter specification, avoid relying only on “H13” or “ISO 45 H.” Make the acceptance criteria explicit.
Your specification should state:
- The applicable standard and version
- The required filter class
- Minimum integral efficiency or maximum penetration at MPPS
- Local efficiency or leakage requirements
- Test airflow and maximum initial pressure drop
- Filter dimensions, frame material, gasket position, and sealing method
- Whether individual testing is required
- Required test-report content and serial-number traceability
- Whether alternative classes or test methods require written approval
A clear specification might read:
“Supply HEPA filters to EN 1822-1:2019, class H14, with a minimum integral efficiency of 99.995% at MPPS and the applicable local-efficiency requirement. Each filter shall be individually tested and supplied with a serial-number-traceable test report showing airflow, efficiency/penetration, leakage-test method and result, initial pressure drop, test date, and conformity status.”
This wording reduces ambiguity and gives both parties a measurable basis for inspection and acceptance.
Conclusion
EN 1822 and ISO 29463 both provide a rigorous way to classify HEPA and ULPA filters using MPPS performance. EN 1822 remains familiar in European specifications, while ISO 29463 supports international procurement and supplier qualification.
When specifying filters, do not stop at the class name. Define the standard version, MPPS efficiency, local leakage requirement, test airflow, individual testing, and documentation requirements. That approach protects your project from ambiguous quotations, incomplete test reports, and costly acceptance delays.
If you are unsure how to select the right HEPA or ULPA air filter for your project, please contact the Cencarb team for expert guidance and recommendations.


